Configuration and monitoring by way of detachable display front (PR 4511/4501); process calibration, signal and relay simulation.
Advanced relay configuration, e.g. setpoint, window, delay, sensor error indication and power monitoring.
Copying of the configuration from one device to others of the same type via the display front.
TC inputs with internal CJC or external CJC for higher accuracy.
Active / passive mA output via the same two terminals.
Application
The device can be mounted in and receive signals from non-classified area and zone 2.
Conversion and scaling of temperature, voltage, potentiometer and linear resistance signals.
Power supply and signal isolator for 2-wire transmitters.
Monitoring of error events and cable breakage via the individual status relay and/or a collective electronic signal via the power rail.
9116A has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.
Technical characteristics
1 green and 1 red front LED indicate operation status and malfunction. 1 yellow LED indicates relay status.
2.6 kVAC galvanic isolation between input, output and supply.
Input for RTD, TC, Ohm, potentiometer, mA and V
Supply for 2-wire transmitters
Active / passive mA output and relay output
Can be supplied separately or installed on power rail, PR type 9400
SIL 2-certified via Full Assessment
Mounting
The devices can be mounted vertically or horizontally without distance between neighbouring units.
9116B
Advanced features
Configuration and monitoring by way of detachable display front (PR 4501); process calibration, signal and relay simulation.
Advanced relay configuration, e.g. setpoint, window, delay, sensor error indication and power monitoring.
Copying of the configuration from one device to others of the same type via PR4501.
Reduced Uo Ex data < 8.3 V for active input signals.
TC inputs with internal CJC or external CJC for higher accuracy.
Active / passive mA output via the same two terminals.
Application
9116B can be mounted in the safe area and in zone 2 / cl. 1 div. 2 and receive signals from zone 0, 1, 2 and zone 20, 21, 22 including M1 / Class I/II/III, Div. 1, Gr. A-G.
Conversion and scaling of temperature, voltage, potentiometer and linear resistance signals.
Power supply and signal isolator for 2-wire transmitters.
Monitoring of error events and cable breakage via the individual status relay and/or a collective electronic signal via the power rail.
The 9116 has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.
Technical characteristics
1 green and 1 red front LED indicate operation status and malfunction. 1 yellow LED indicates relay status.
2.6 kVAC galvanic isolation between input, output and supply.
Input for RTD, TC, Ohm, potentiometer, mA and V
Supply for 2-wire transmitters
Active / passive mA output and relay output
Can be supplied separately or installed on power rail, PR type 9400
SIL 2-certified via Full Assessment
Mounting
The devices can be mounted vertically or horizontally without distance between neighbouring units.